Siemens digital expansion module. The Siemens SM 1223 PLC digital expansion module is an 8 input a...

Best current price£102.05from Amazon

All Offers

5 offers from £102.05 - £560.27

View price history by clicking the chart icon.

AmazonSiemens ST70-1200 Digital SM 1223 8 Module Input 8 Output Transistor 0.5A
Free delivery in 1–3 days
£102.05
Visit shop
eBaySiemens 6ES7223-1BH32-0XB0 SM 1223 Digital Input / Output Module
Free delivery in 1–3 days
£249.52
Visit shop
Tameson UKSiemens Simatic Plc Digital Input And Output Module - 6Es72231bh320xb0
Free delivery in 1–3 days
£273.25
Visit shop

Product Information

Full details

This Siemens SM 1223 digital expansion module is designed for industrial automation engineers and system integrators working with SIMATIC S7-1200 series PLCs. It provides a robust 8 digital inputs and 8 relay outputs, enabling seamless integration of digital signals into control systems. A key benefit is its advanced diagnostics and alarm capabilities, simplifying troubleshooting. However, users should note that the output current rating is limited to 500mA per channel, which may require careful consideration for high-power loads.

All features

BrandSiemens

Extended Product Information

FAQs

What is the maximum output current for the relay outputs?

The maximum output current for each relay output is 500mA.

Can I use this module with S7-300 PLCs?

No, this module is specifically designed for and compatible only with the Siemens SIMATIC S7-1200 series PLCs.

What type of power supply is required?

The module requires a 24VDC power supply, with a permitted voltage range of 20.4V to 28.8V DC.

Does the module provide electrical isolation?

Yes, it features galvanic isolation between the channels and the backplane bus for enhanced reliability and safety.

What is the operating temperature range?

The module can operate reliably in ambient temperatures ranging from -20°C to 60°C.

Are the inputs and outputs configurable?

Yes, the digital inputs are configurable for sink or source, and the digital outputs are configurable.

What is the maximum shielded cable length for digital inputs?

The maximum shielded cable length for digital inputs is 500 meters.

Troubleshooting

Module not recognized by PLC

Verify correct physical installation on the S7-1200 rail. Ensure the module is properly seated and has power. Check the configured I/O addresses in the PLC programming software for conflicts or errors.

Digital inputs not functioning

Confirm the input voltage is within the 0-30V DC range and matches the expected sink/source configuration. Check wiring connections for looseness or incorrect polarity. Test input signals directly with a multimeter.

Relay outputs not activating

Ensure the output current does not exceed the 500mA rating. Verify the output voltage is within the permitted range (20.4-28.8V DC for DC outputs). Check PLC program logic controlling the output. Inspect output wiring for damage.

Module reporting diagnostic error

Consult the S7-1200 system manual for specific diagnostic codes related to this module. Common causes include power supply issues, internal faults, or over-temperature conditions. Check the environmental conditions and power stability.

Pros and Cons

Pros

  • Seamless integration with SIMATIC S7-1200 PLCs.
  • Versatile I/O configuration with support for sink/source inputs.
  • Enhanced system safety and reliability due to galvanic isolation.
  • Advanced diagnostics and alarm features for improved operational insight.
  • Robust operating temperature range for industrial applications.

Cons

  • Relay output current limited to 500mA per channel.
  • Requires a 24VDC power supply.
  • Specific compatibility restricted to S7-1200 series.
  • Signal change delay of up to 12.8ms might be unsuitable for ultra-high-speed applications.

Setup, Compatibility & Care

Setup: This module is designed for use with Siemens SIMATIC S7-1200 series PLCs. Ensure the PLC is powered off before installing the module. Slide the module onto the designated rail of the S7-1200 CPU or a preceding expansion module until it clicks into place. Connect the 24VDC power supply to the appropriate terminals. Wire the digital inputs and outputs according to your application requirements, adhering to the specified voltage and current limits. Configure the module's I/O addresses within the S7-1200 programming software.

Compatibility: This module is exclusively compatible with the Siemens SIMATIC S7-1200 PLC series. Refer to the specific S7-1200 CPU documentation for the maximum number of expansion modules supported.

Care: Keep the module clean and free from dust and moisture. Use a dry or slightly damp cloth for cleaning; avoid harsh chemicals or solvents. Ensure adequate ventilation around the module and the PLC system to prevent overheating, especially within the specified operating temperature range of -20°C to 60°C.